+91-9072707561 ​ | +916374994856

GAZCHAMP-EX

Gazchamp–Ex is the till date most preferred Multi Gas Detector with Individual Display type Gas Monitor. Gazchamp-Ex has established itself in the market with most useful features and ease of maintenance clubbed together. Each channel has separate input card maintaining single loop integrity most desired in reliable Gas Detection system. Gazchamp-Ex can be connected with various Tritech make direct Detectors or to any / mix of various Gas transmitters .

Individual relay contacts, 4-20 mA output and expandable nature are the key other features of Gazchamp-Ex. It’s available in 8 / 16 channel configuration. Special versions are available with Battery backups in case of power failures.

Gazchamp-Ex is most ideally suitable for plants which require Multi Channel Gas Detection system for various Gases or for single Gas application but with compact Monitor.

Download Brochure

  • Fast response on Gas leak
  • Individual Digital display for each channel
  • Detector certified flameproof
  • Uses reliable long life sensor
  • Independent monitor card for each detector
  • Temperature compensator to avoid false Alarm
  • Hooter & Reset switch mounted at the bottom to avoid Water ingress
  • User adjustable Alarm levels
  • Relay Contacts for AL1, AL2 & Fault
  • On site calibration facility
  • IIA – IIB, Optionally IIC certified by CCOE ( PESO ) / ERTL (E)
  Combustible Toxic Oxygen
Range 0- 100% LEL
Combustible gas
CI2:0 – 5 upto 50 PPM

 

S02:0 – 10 PPM

 

HCN:0 – 25 PPM

 

H2S:0 – 100 PPM

 

CO:0 – 999 PPM

 

VOC:0 – 999 PPM

 

NH3:0 – 999 PPM

 

(Other Gases on Request)

0 – 5, 10, 15, 20, 25,
30% V/V O2
Detector Type Direct Connect OR 3 Wire Transmitter 2 Wire Transmitter 2 Wire Transmitter
Sensor Principle Catalytic Bead OR Infrared Electrochemical OR Semiconductor Electrochemical
Display / Resolution 2 or 3 digits LED Display / 1 or 0.1
Indicators 2 nos. Red LED for Alarm 1 & Alarm 2
1 no. Red LED for Over Range
Amber LED for Fault
Green LED for Pilot
Alarms Two Adjustable Alarm Levels (User Adjustable)
Contacts Common : SPDT Potential free Contacts for Alarm 1, Alarm 2 & Fault
Individual : SPDT Potential free Contacts for Alarm 1 of each Channel
SPDT Potential free Contacts for Alarm 2 of each Channel
Contacts Rated 230V AC, 5 Amp / 12 VDC, 10 Amp
Retransmission Non-isolated 4 – 20 mA O/P (instead of Individual Relay Contacts)
Power Supply 230 V AC or 110 V AC, 50 Hz, Others on request
Dimensions 2 ~ 8 Channels : 385 mm(W) x 320 mm(H) x 125 mm(D)
9 ~ 15 Channels : 500 mm(W) x 360 mm(H) x 158 mm(D)
Mounting ABS Plastic, Wall / Surface Mounted
Protection Dust and Weather protected
Operating Temp. 0 – 60 Degrees Centigrade
Humidity 0 – 95% RH, Non-Condensing